If you are mounting an EX2200 switch in a rack or cabinet with other equipment, or if
you are placing it on the desktop or floor near other equipment, ensure that the exhaust
from other equipment does not blow into the intake vents of the chassis.
Leave at least 24 in. (61 cm) in front of the switch and 6 in. (15.2 cm) behind the switch.
For service personnel to remove and install hardware components, you must leave
adequate space at the front and back of the switch. NEBS GR-63 recommends that
you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and 24 in. (61 cm)
behind the rack or cabinet.
Related
Documentation
Rack Requirements for EX2200 Switches on page 39
Cabinet Requirements for EX2200 Switches on page 40
General Site Guidelines for EX Series Switches on page 35
Rack-Mounting and Cabinet-Mounting Warnings for EX Series Switches on page 129
Cooling System and Airflow in an EX2200 Switch on page 15